Product Overview
YGG silicone rubber cable is manufactured in full compliance with GB/T 5013.8 standards for high-temperature industrial applications. Featuring tinned copper conductors and dual-layer silicone rubber construction, this cable delivers reliable performance in continuous 180°C environments. Ideal for fixed wiring in furnaces, kilns, and thermal processing equipment.
Key Features & Benefits
-
GB/T 5013.8 Certified: Full compliance with Chinese national standard
-
180°C Continuous Rating: Verified thermal endurance per GB/T 5013.8
-
Chemical Resistance: Resists oils, acids, and industrial solvents
-
Flexible Performance: Operational range -60°C to +180°C
-
Corrosion Protection: Tinned copper conductors
-
Halogen-Free Safety: Low smoke, non-toxic combustion
Construction
Layer | Material Specification | Standard Reference |
---|---|---|
Conductor | Tinned Copper Strands (Class 5 flexibility) | IEC 60228 |
Insulation | Silicone Rubber Compound | GB/T 5013.8 |
Outer Sheath | Silicone Rubber | GB/T 5013.8 |
Technical Data
Parameter | Specification | Test Standard |
---|---|---|
Rated Voltage | 450/750V AC | GB/T 5013.8 |
Temperature Range | Continuous: -60°C to +180°C | GB/T 5013.8 |
Short-Circuit Temp | +250°C (max 5s) | IEC 60331 |
Min. Bending Radius | 6 × Cable Diameter | GB/T 5013.8 |
Insulation Resistance | ≥0.011 MΩ·km (20°C) | GB/T 3048.6 |
Conductor Sizes | 0.75mm² - 240mm² | GB/T 3956 |
Voltage Test | 2500V AC, 5min | GB/T 3048.8 |
Applications
-
Industrial furnace wiring systems
-
Kiln and heat treatment equipment connections
-
Boiler room installations in power plants
-
Fixed wiring in steel mills and foundries
-
High-temperature zones in glass manufacturing
Engineering Selection Guide
-
Standard Compliance
-
Valid for GB/T 5013.8 projects
-
Indoor use only (not UV-stable for outdoor applications)
-
-
Temperature Limits
-
Maximum continuous operating temperature: 180°C
-
Short-circuit withstand: 250°C for ≤5 seconds
-
-
Installation Requirements
-
Fixed installations only (no continuous flexing)
-
Maintain minimum 6×OD bending radius
-
Protect against sharp edges and abrasion
-
-
Electrical Parameters
-
Rated for 450/750V AC systems
-
Conductor sizing per GB/T 3956 standards
-
Standards Compliance
Standard | Scope |
---|---|
GB/T 5013.8 | Silicone rubber insulated cables |
GB/T 3956 | Conductor requirements |
GB/T 3048 | Electrical test methods |
IEC 60245-8 | International equivalent standard |