NMD90 Non-Metallic Sheathed Cable Technical Specifications

NMD90 Non-Metallic Sheathed Cable Technical Specifications

Conductor Insulation Ground Approx. Jacket thickness Approx. Cable Dia. Approx. Cable weight Allowabl e Ampaciti
es 30°C
Size (AWG) Cores Strands Inches mm Size (AWG) Core Inches mm Inches mm Ib/ 1000ft Kg/ km
14 2 1 0.034 0.86 14 1 0.030 0.76 0.388*0.192 9.86*4.88 68 101 25*
14 2 1 0.034 0.86 14 1 0.030 0.76 0.388 x 0.192 9.86 x 4.88 68 101 25*
12 2 1 0.034 0.86 14 1 0.030 0.76 0.422 x 0.209 10.71 x 5.30 86 129 30*
10 2 1 0.034 0.86 12 1 0.030 0.76 0.481 x 0.230 12.21 x 5.84 122 182 40*
8 2 7 0.040 1.02 10 1 0.045 1.14 0.636 x 0.312 16.15 x 7.92 208 310 55
6 2 7 0.051 1.30 8 7 0.045 1.14 0.792 x 0.370 20.12 x 9.40 315 468 75
14 3 1 0.034 0.86 14 1 0.030 0.76 0.345 8.77 86 128 25*
12 3 1 0.034 0.86 14 1 0.030 0.76 0.381 9.69 114 169 30*
10 3 1 0.034 0.86 12 1 0.030 0.76 0.427 10.85 163 242 40*
8 3 7 0.040 1.02 10 1 0.045 1.14 0.570 14.47 275 408 55
6 3 7 0.051 1.30 8 7 0.045 1.14 0.695 17.65 421 627 75
3 3 7 0.051 1.30 6 7 0.080 2.03 0.925 23.48 799 1189 115

Note: Ampacities marked with an asterisk (*) are for single-phase residential services as per the Canadian Electrical Code. Always consult the latest applicable codes and standards for final design and installation requirements.

Product Details