0.6/1kV XLPE/SWA/LSZH Armoured Power Cable | 3-4 Core 1.5-400mm² | IEC 60502-1 | Fire-Safe Construction

0.6/1kV XLPE/SWA/LSZH Armoured Power Cable | 3-4 Core 1.5-400mm² | IEC 60502-1 | Fire-Safe Construction

Product Overview

This Copper/XLPE/PVC/SWA/LSZH Power Cable (600/1000V) integrates steel wire armour (SWA) and zero-halogen sheathing for critical installations where mechanical protection and fire safety are paramount. Compliant with IEC 60502-1 and BS 6724, it ensures circuit integrity while minimizing toxic emissions during fires.


Key Specifications

Parameter Specification
Standards IEC 60502-1, BS 6724, IEC 60754-1/2, IEC 61034
Conductor Class 2 Stranded Copper (IEC 60228)
Insulation XLPE (90°C operational)
Bedding PVC Layer
Armour Galvanized Steel Wire (SWA)
Sheath LSZH (Low Smoke Zero Halogen)
Voltage 600/1000V
Temperature -20°C to +90°C
Bending Radius 6ר (≤16mm²) / 8ר (≥25mm²)

Technical Data Tables

3-Core Configuration

Section (mm²) Cond. Ø (mm) Insul. Thk. (mm) Armour Dia. (mm) Sheath Thk. (mm) Overall Ø (mm)
1.5 1.4 0.7 0.8 1.8 13.2
2.5 1.8 0.7 0.8 1.8 14.1
4 2.3 0.7 0.8 1.8 15.2
6 2.8 0.7 1.25 1.8 17.1
10 3.6 0.7 1.25 1.8 18.9
16 4.5 0.7 1.25 1.8 20.8
25 5.6 0.9 1.6 1.8 24.7
35 6.7 0.9 1.6 1.8 27.2
50 8.0 1.0 1.6 1.9 30.6
70 9.4 1.1 2.0 2.1 35.2
95 11.0 1.1 2.0 2.2 39.3
120 12.4 1.2 2.0 2.3 43.0
150 13.8 1.4 2.5 2.5 48.6
185 15.3 1.6 2.5 2.7 53.0
240 17.5 1.7 2.5 2.8 58.5
300 19.5 1.8 2.5 3.0 64.0
400 22.6 2.0 3.15 3.3 73.5

4-Core Configuration

Section (mm²) Cond. Ø (mm) Insul. Thk. (mm) Armour Dia. (mm) Sheath Thk. (mm) Overall Ø (mm)
1.5 1.4 0.7 0.8 1.8 14.0
2.5 1.8 0.7 0.8 1.8 14.9
4 2.3 0.7 1.25 1.8 17.0
6 2.8 0.7 1.25 1.8 18.2
10 3.6 0.7 1.25 1.8 20.2
16 4.5 0.7 1.6 1.8 23.0
25 5.6 0.9 1.6 1.8 26.7
35 6.7 0.9 1.6 1.9 29.5
50 8.0 1.0 2.0 2.1 34.2
70 9.4 1.1 2.0 2.2 38.8
95 11.0 1.1 2.0 2.3 42.9
120 12.4 1.2 2.5 2.5 48.6
150 13.8 1.4 2.5 2.7 53.2
185 15.3 1.6 2.5 2.8 58.1
240 17.5 1.7 2.5 3.1 64.8
300 19.5 1.8 2.5 3.2 70.4
400 22.6 2.0 3.15 3.6 81.3

*Weight data available in technical dossier


Product Advantages

  • 🔥 Fire Survival: LSZH sheath reduces smoke density (>60% light transmittance) and eliminates acid gas (HCl <0.5%) per IEC 61034/60754

  • ⚔️ Mechanical Defense: SWA armour withstands 3000N crushing force (IEC 60229) and rodent penetration

  • ⚡ EMI Shielding: Steel wire armour blocks electromagnetic interference

  • 🌧️ All-Environment Durability: Moisture-resistant PVC bedding + UV-stable LSZH for outdoor/direct burial

  • 🛠️ Installation Flexibility: Compact bending radius (6-8× cable Ø) simplifies routing


Application Scenarios

Environment Use Case
Life-Safety Systems Hospital ICU circuits, tunnel emergency lighting
High-Risk Industry Petrochemical plants, offshore platforms
Public Spaces Airports, metro stations, shopping malls
Energy Infrastructure Substations, wind farm power collection

Suitable for: Direct burial • Cable ducts • Trays • Hazardous areas (IEC 60079)


Compliance & Packaging

  • Fire Certifications:

    • Flame propagation: IEC 60332-3 Cat. A

    • Toxicity: IEC 60754-1/2

    • Smoke density: IEC 61034-2

  • Packaging: Export wooden drums (Custom lengths/drum sizes)