Product Overview
HUATONG UL 1063-certified 6AWG MTW/THHN cable delivers robust performance for industrial power distribution. Featuring 19-strand bare copper conductors, dual-layer PVC/nylon insulation, and VW-1 flame resistance, this 600V-rated cable operates at 90°C in dry environments with exceptional oil/gasoline resistance (Type II).
Key Applications
-
Industrial machinery control wiring
-
CNC equipment & automation systems
-
Motor feeder circuits
-
Manufacturing plant power distribution
-
NEC-compliant cable tray installations (CT-rated for 1/0 AWG+)
Construction & Materials
Component | Specification |
---|---|
Conductor | 19-strand bare annealed copper (ASTM B3/B8/B787) |
Insulation | Color-coded PVC • Flame-retardant • Moisture-resistant |
Outer Covering | Polyamide (Nylon) • Abrasion/oil resistant |
Temperature | 90°C dry rating |
Voltage | 600V AC |
Technical Specifications: 6AWG Model
Parameter | Imperial | Metric |
---|---|---|
Stranding | 19x0.080" | 19x2.032mm |
Insulation Thickness | 0.030 in | 0.76 mm |
Nylon Thickness | 0.005 in | 0.13 mm |
Overall Diameter | 0.26 in | 6.60 mm |
Weight | 98 lbs/kft | 145 kg/km |
Ampacity (75°C) | 65A | NEC Table 310.16 |
*Full AWG range available: 14-750 kcmil*
Certifications & Compliance
UL/CSA(C22.2 No.75-03) NEC(Article 310)
-
Primary Standards: UL 83 • UL 1063 • NEMA WC70/ICEA S-95-658
-
Safety Compliance: NFPA 70/79 • OSHA 29 CFR 1910
-
Environmental: RoHS compliant • Gasoline/Oil Resistant II
Performance Features
-
Mechanical Durability
-
Nylon jacketing withstands 5,000+ flex cycles (ASTM D430)
-
Abrasion resistance: >100 cycles (UL 719 scrape test)
-
-
Chemical Resistance
-
Passes UL 62 oil immersion test (7-day @ 121°C)
-
Sunlight resistant (UV stability per UL 1581)
-
-
Electrical Safety
-
VW-1 flame rating (UL 2556 vertical tray test)
-
100% spark-tested conductors
-
Engineering Data Comparison
AWG | Strands | OD (mm) | Weight (kg/km) | Max Ampacity |
---|---|---|---|---|
14 | 19 | 2.79 | 24 | 20A |
10 | 19 | 4.32 | 58 | 30A |
6 | 19 | 6.60 | 145 | 65A |
2 | 19 | 9.91 | 357 | 100A |
1/0 | 19 | 13.21 | 695 | 125A |
Ampacity based on 75°C conductor rating per NFPA 79
Installation Guidelines
Application | Bending Radius | Conduit Fill % | Torque (lb-in) |
---|---|---|---|
Machine Tools | 5x OD | 40% max | 25-30 |
Cable Trays | 6x OD | N/A | N/A |
Control Panels | 4x OD | 50% max | 15-20 |
-
Sunlight Rating: Valid for 6AWG+ in all colors
-
Oil Exposure: Limit to 60°C in wet locations
Color Coding & Identification
-
Standard: Black, White, Red, Green, Blue, Yellow
-
Custom: Orange, Brown, Purple, Grey, Pink, Tan (MOQ 2,000 ft)
-
Phase Identification per NEC 200.6