UL 1063 6AWG MTW/THHN Copper Cable | 600V 90°C Oil-Resistant | NEMA WC70 Compliant

Industrial-Grade MTW/THHN Cable

Product Overview

HUATONG UL 1063-certified 6AWG MTW/THHN cable delivers robust performance for industrial power distribution. Featuring 19-strand bare copper conductors, dual-layer PVC/nylon insulation, and VW-1 flame resistance, this 600V-rated cable operates at 90°C in dry environments with exceptional oil/gasoline resistance (Type II).


Key Applications

  • Industrial machinery control wiring

  • CNC equipment & automation systems

  • Motor feeder circuits

  • Manufacturing plant power distribution

  • NEC-compliant cable tray installations (CT-rated for 1/0 AWG+)


Construction & Materials

Component Specification
Conductor 19-strand bare annealed copper (ASTM B3/B8/B787)
Insulation Color-coded PVC • Flame-retardant • Moisture-resistant
Outer Covering Polyamide (Nylon) • Abrasion/oil resistant
Temperature 90°C dry rating
Voltage 600V AC

Technical Specifications: 6AWG Model

Parameter Imperial Metric
Stranding 19x0.080" 19x2.032mm
Insulation Thickness 0.030 in 0.76 mm
Nylon Thickness 0.005 in 0.13 mm
Overall Diameter 0.26 in 6.60 mm
Weight 98 lbs/kft 145 kg/km
Ampacity (75°C) 65A NEC Table 310.16

*Full AWG range available: 14-750 kcmil*


Certifications & Compliance

UL/CSA(C22.2 No.75-03)   NEC(Article 310)

  • Primary Standards: UL 83 • UL 1063 • NEMA WC70/ICEA S-95-658

  • Safety Compliance: NFPA 70/79 • OSHA 29 CFR 1910

  • Environmental: RoHS compliant • Gasoline/Oil Resistant II


Performance Features

  1. Mechanical Durability

    • Nylon jacketing withstands 5,000+ flex cycles (ASTM D430)

    • Abrasion resistance: >100 cycles (UL 719 scrape test)

  2. Chemical Resistance

    • Passes UL 62 oil immersion test (7-day @ 121°C)

    • Sunlight resistant (UV stability per UL 1581)

  3. Electrical Safety

    • VW-1 flame rating (UL 2556 vertical tray test)

    • 100% spark-tested conductors


Engineering Data Comparison

AWG Strands OD (mm) Weight (kg/km) Max Ampacity
14 19 2.79 24 20A
10 19 4.32 58 30A
6 19 6.60 145 65A
2 19 9.91 357 100A
1/0 19 13.21 695 125A

Ampacity based on 75°C conductor rating per NFPA 79


Installation Guidelines

Application Bending Radius Conduit Fill % Torque (lb-in)
Machine Tools 5x OD 40% max 25-30
Cable Trays 6x OD N/A N/A
Control Panels 4x OD 50% max 15-20
  • Sunlight Rating: Valid for 6AWG+ in all colors

  • Oil Exposure: Limit to 60°C in wet locations


Color Coding & Identification

  • Standard: Black, White, Red, Green, Blue, Yellow

  • Custom: Orange, Brown, Purple, Grey, Pink, Tan (MOQ 2,000 ft)

  • Phase Identification per NEC 200.6