NSHTÖU 0.6/1kV Rubber Insulated Flexible Cable – Technical Specifications

parameter
Table 1
Number and cross-sectional area of conductor Maximum diameter of wires in conductor Nominal thickness of insulation Nominal thickness of sheath Approximate overall diameter Approximate net weight of cables Maximum conductor resistance at 200C
Inner Outer
n x mm2 mm mm mm mm kg/km Ω/km
3x1.5 0.26 0.8 1.0 1.6 11.9 204 13.7
3x2.5 0.26 0.9 1.0 1.6 13.3 268 8.21
3x4 0.31 1.0 1.2 2.0 17.4 392 5.09
3x6 0.31 1.0 1.2 2.0 18.6 478 3.39
3x10 0.41 1.2 1.4 2.2 22.5 727 1.95
3x16 0.41 1.2 1.4 2.2 25.0 961 1.24
3x25 0.41 1.4 1.6 2.5 29.4 1391 0.795
3x35 0.41 1.4 1.8 3.0 32.3 1820 0.565
3x50 0.41 1.6 2.0 3.5 38.9 2596 0.393
3x70 0.51 1.6 2.0 3.5 42.8 3335 0.277
3x95 0.51 1.8 2.4 4.0 50.0 4458 0.210
3x120 0.51 1.8 2.4 4.0 52.3 5272 0.164
3x150 0.51 2.0 2.4 4.0 57.2 6401 0.132
3x240 0.51 2.4 3.2 5.0 69.0 10554 0.0817
Table 2
Number and cross-sectional area of conductor Maximum diameter of wires in conductor Nominal thickness of insulation Nominal thickness of sheath Approximate overall diameter Approximate net weight of cables Maximum conductor resistance at 200C
Inner Outer
n x mm2 mm mm mm mm kg/km Ω/km
4x1.5 0.26 0.8 1.0 1.6 12.7 238 13.7
4x2.5 0.26 0.9 1.2 2.0 15.5 360 8.21
4x4 0.31 1.0 1.2 2.0 18.5 463 5.09
4x6 0.31 1.0 1.2 2.0 19.9 571 3.39
4x10 0.41 1.2 1.4 2.2 24.2 878 1.95
4x16 0.41 1.2 1.6 2.5 26.7 1212 1.24
4x25 0.41 1.4 1.8 3.0 32.1 1821 0.795
4x35 0.41 1.4 1.8 3.0 33.8 2380 0.565
4x50 0.41 1.6 2.0 3.5 41.0 3368 0.393
4x70 0.51 1.6 2.0 3.5 46.0 4367 0.277
4x95 0.51 1.8 2.4 4.0 54.3 5562 0.210
4x120 0.51 1.8 2.8 4.5 57.3 6873 0.164
4x150 0.51 2.0 2.8 4.5 64.2 8350 0.132
Table 3
Number and cross-sectional area of conductor Maximum diameter of wires in conductor Nominal thickness of insulation Nominal thickness of sheath Approximate overall diameter Approximate net weight of cables Maximum conductor resistance at 200C
Inner Outer
n x mm2 mm mm mm mm kg/km Ω/km
5x1.5 0.26 0.8 1.0 1.6 13.6 269 13.7
5x2.5 0.26 0.9 1.2 2.0 16.6 421 8.21
5x6 0.31 1.0 1.4 2.2 21.4 764 3.39
5x10 0.41 1.2 1.4 2.2 25.0 1072 1.95
5x16 0.41 1.2 1.6 2.5 29.0 1533 1.24
7x1.5 0.26 0.8 1.2 2.0 16.9 415 13.7
7x2.5 0.26 0.9 1.2 2.0 19.1 556 8.21
7x4 0.31 1.0 1.4 2.2 22.7 796 5.09
10x4 0.31 1.0 1.4 2.2 26.0 1007 5.09
12x1.5 0.26 0.8 1.4 2.2 20.3 599 13.7
12x2.5 0.26 0.9 1.4 2.2 23.1 813 8.21
18x1.5 0.26 0.8 1.4 2.2 22.9 789 13.7
18x2.5 0.26 0.9 1.6 2.5 27.3 1156 8.21
18x4 0.31 1.0 1.8 3.0 43.4 1837 5.09
Table 4
Number and cross-sectional area of conductor Maximum diameter of wires in conductor Nominal thickness of insulation Nominal thickness of sheath Approximate overall diameter Approximate net weight of cables Maximum conductor resistance at 200C
Inner Outer
n x mm2 mm mm mm mm kg/km Ω/km
24x1.5 0.26 0.8 1.4 2.2 26.0 985 13.7
24x2.5 0.26 0.9 1.4 2.2 31.1 1454 8.21
36x1.5 0.26 0.8 1.6 2.5 30.0 1297 13.7
36x2.5 0.26 0.9 1.8 3.0 36.3 2075 8.21
37x1.5 0.26 0.8 1.6 2.5 31.0 1343 13.7
3x2.5+1.5 0.26/0.26 0.9/0.8 1.2 2.0 16.5 346 8.21/13.7
3x4+2.5 0.31/0.26 1.0/0.9 1.2 2.0 18.1 439 5.09/8.21
3x6+2.5 0.31/0.26 1.0/0.9 1.2 2.0 19.2 520 3.39/8.21
3x6+4 0.31/0.31 1.0/1.0 1.2 2.0 19.6 544 3.39/5.09
3x16+10 0.41/0.41 1.2/1.2 1.6 2.5 27.3 1164 1.24/1.95
3x25+16 0.41/0.41 1.4/1.2 1.8 3.0 32.2 1698 0.795/1.24
3x35+16 0.41/0.41 1.4/1.2 1.8 3.0 33.5 2021 0.565/1.24
3x70+35 0.51/0.41 1.6/1.4 2.0 3.9 46.0 4123 0.277/0.565
3x95+50 0.51/0.41 1.8/3.8 2.4 4.0 53.0 5515 0.210/0.393
3x150+3x70/3 0.51/0.41 2.0/1.4 2.4 4.0 56.1 7195 0.132/0.277
3x185+3x95 0.51/0.41 2.2/1.4 2.8 4.5 63.4 9150 0.108/0.210
3x240+3x95/3 0.51/0.41 2.2/1.4 3.2 5.0 69.1 11290 0.0817/0.210
3x240+3x120/3 0.51/0.41 2.2/1.4 3.2 5.0 69.1 11290 0.0817/0.164

Current rating

Number of loaded cores 2 or 3 *, **
Conductor cross-section in mm2 Current rating, A
1.5 18
2.5 26
4 34
6 44
10 61
16 82
25 108
35 135
50 168
70 207
95 250
120 292
150 335
185 378

Current rating as defined to DIN VDE 0298-4. Ambient air temperature: 30°C. Operating temperature at conductor 600C.