Product Overview
High-Reliability Underground Power Transmission
Designed for critical primary distribution networks, this 15kV 133% IL power cable features 3/C 3/0 AWG copper conductors with TR-XLPE insulation and a sunlight-resistant LLDPE sheath. Certified to UL 1072 and AEIC CS-8 standards, it delivers superior performance in direct burial, conduit systems, and wet/dry locations at temperatures up to 105°C. Ideal for utility grids, industrial campuses, and renewable energy projects.
Key Specifications
| Parameter | Specification |
|---|---|
| Voltage Rating | 15kV (133% insulation level) |
| Conductor | 3×3/0 AWG soft annealed copper (ASTM B3/B8) |
| Insulation | Thermoplastic-Reinforced XLPE (TR-XLPE) |
| Metallic Shield | Copper wire shield (ASTM B3) |
| Jacket | Linear Low-Density Polyethylene (LLDPE), black |
| Temperature Range | -40°C to +105°C (90°C continuous operation) |
| Certifications | UL 1072, AEIC CS-8, ICEA S-94-649, ANSI/OCA S-94-649 |
Cable Construction
| Layer | Material & Function |
|---|---|
| 1. Conductor | 3/0 AWG compressed stranded copper · Low impedance · High fault-current capacity |
| 2. Conductor Shield | Semi-conducting XLPE · Smooths electric field gradients |
| 3. Insulation | TR-XLPE · 133% insulation level · Superior dielectric strength |
| 4. Insulation Shield | Semi-conducting XLPE · Prevents partial discharge |
| 5. Metallic Shield | Helically applied copper wires · Manages ground-fault currents |
| 6. Jacket | LLDPE · UV/oil/chemical resistant · -40°C cold impact rating |
Technical Advantages
-
Enhanced Safety
-
133% insulation level withstands 15kV surges + transient overvoltages.
-
-
Environmental Resistance
-
LLDPE jacket resists moisture, acids, alkalis, and UV degradation.
-
-
Fault Resilience
-
Copper wire shield handles 25kA fault currents (AEIC CS-8 compliant).
-
-
Long Service Life
-
TR-XLPE insulation maintains integrity at 105°C for 40+ years.
-
-
Easy Identification
-
Surface-printed jacket with lightning bolt symbol (red stripes optional).
-
Applications
-
Utility Primary Distribution: Underground feeder lines (≤15kV).
-
Industrial Complexes: Power networks in refineries, chemical plants.
-
Direct Burial: Conduit-free trench installations.
-
Solar/Wind Farms: Grid interconnection cables.
-
Flood-Prone Areas: Moisture-blocking design (ICEA T-31-610 compliant).
Performance Data
| Characteristic | Value | Test Standard |
|---|---|---|
| Max Operating Temp | 90°C (normal) / 140°C (emergency) | UL 1072 |
| Short Circuit Rating | 250°C for 5 seconds | AEIC CS-8 |
| Bending Radius | 18× cable diameter | ICEA S-94-649 |
| Water Penetration | 15 psi / 60 min (optional sealed strand) | ICEA T-31-610 |
| Jacket Thickness | 85 mil (2.16 mm) | ANSI/OCA S-94-649 |
Standards Compliance
| Standard | Requirement |
|---|---|
| UL 1072 | Medium Voltage Power Cable Safety |
| AEIC CS-8 | Utility Cable Performance (5kV-46kV) |
| ICEA S-94-649 | Shielded Power Cable Construction |
| RUS 1728F-U1 | USDA Rural Utilities Service Approval |
Engineering Selection Guide
-
For High-Corrosion Zones: Specify LLDPE jacket (superior to PVC in chemical resistance).
-
Fault-Prone Networks: Copper wire shield (not tape) for better current dissipation.
-
Cold Climates: -40°C rated sheath maintains flexibility in Arctic conditions.
-
Identification: Request red stripes for phase differentiation in duct banks.
Note: Custom configurations (neutral wires, armor, fire rating) available. Request ICEA test reports for water-blocking verification.
