Product Overview:
This UL 854 Listed and Certified USE/USE-2 Aluminum Conductor Cable delivers reliable underground power transmission for service entrance and solar PV applications. Engineered with XLPE insulation and compact-stranded AA-8000 aluminum alloy conductors, it meets rigorous safety standards while offering cost-effective performance in direct burial installations.
Technical Specifications
Parameter | Specification |
---|---|
Standard | UL 854 (USE/USE-2), NEC Article 338 & 690 |
Voltage Rating | 600V AC |
Temp Rating | 90°C Wet/Dry Locations |
Conductor | AA-8000 Al Alloy (ASTM B800), Compact Stranded |
Insulation | Cross-Linked Polyethylene (XLPE) - Black |
Direct Burial | Yes (NEC Table 300.5 Compliant) |
PV Approved | USE-2 for NEC 690 Solar Arrays |
Flame Rating | UL VW-1 Certified |
Available Sizes | 6 AWG to 1000 kcmil |
Product Construction
-
Conductor
-
Material: AA-8000 Series Aluminum Alloy (ASTM B800)
-
Structure: Compact stranded, annealed temper
-
Benefits: 40% lighter vs copper, corrosion-resistant
-
-
Insulation
-
Material: Cross-Linked Polyethylene (XLPE)
-
Thickness: UL 854 compliant voltage grading
-
Performance: UV-resistant, moisture-blocking
-
Material Properties
Component | Key Characteristics |
---|---|
Al Conductor | ≥61% IACS conductivity, 2.7 g/cm³ density |
XLPE Jacket | Dielectric strength >15 kV/mm, hydrolysis-resistant |
Primary Applications
Underground Service Entrance
-
Utility-to-meter connections (residential/commercial)
Solar PV Systems
-
Panel interconnects (NEC 690 USE-2 compliant)
-
Combiner-to-inverter runs
Direct Burial Feeders
-
Agricultural irrigation systems
-
Parking lot lighting
Engineering Selection Guide
Consideration | Critical Factors |
---|---|
Ampacity | Use NEC Table 310.16 (90°C column) |
Voltage Drop | Calculate via V<sub>drop</sub> = √3 × I × L × Z |
Fault Current | Verify thermal withstand capacity |
Installation | Min. burial depth: 24" (610mm) per NEC 300.5 |
⚠️ Usage Restrictions
-
Not approved for aerial spans
-
Prohibited in conduit with other conductors
-
Aluminum-rated connectors required
Compliance & Certifications
• UL 854 (Service-Entrance Cables)
• UL Subject 758 (AWM Recognition)
• NEC Articles 338, 690 & 300.5
• RoHS 3 Compliant
*Note: USE-2 required for PV applications; standard USE not permitted in solar arrays per NEC 690.31*