Product Overview
The CHJPF96/NC is a robust Fire Resistant and Steel Wire Armored marine communication cable, engineered to ensure the integrity of critical telecommunication, instrumentation, and data systems in the most demanding and high-risk environments. It combines XLPE insulation with mica glass tape for circuit survival during fire, double thermoplastic polyolefin sheaths (SHF1), and a protective galvanized steel wire braid armor. As a Halogen-Free, Low Smoke Fire Resistant (LSHF) cable compliant with IEC 60331, it is designed for applications where both fire safety and superior mechanical protection are non-negotiable.
Key Features & Benefits
-
Guaranteed Fire Survival Performance: Certified to IEC 60331, ensuring continued circuit operation under direct flame exposure, which is critical for emergency and safety-critical communication links.
-
Maximum Mechanical Durability: The galvanized steel wire braid armor (Code 9) provides exceptional protection against physical impact, crushing, and rodent damage, making it ideal for exposed or harsh installation routes.
-
Comprehensive Safety System: Integrates fire resistance with Halogen-Free (IEC 60754) and Low Smoke (IEC 61034) properties to reduce toxic fumes, alongside Flame Retardancy (IEC 60332) to inhibit fire spread, offering a complete safety solution.
-
Robust Environmental Protection: The double-layer thermoplastic polyolefin (SHF1) sheath provides excellent resistance to moisture, oils, and chemicals, ensuring long-term reliability.
Technical Specifications
-
Rated Voltage: 150/250V
-
Maximum Continuous Conductor Temperature: 90°C
-
Available Conductor Cross-Sections: 0.5 mm², 0.75 mm², 1.0 mm², 1.5 mm², 2.5 mm²
-
Core Configuration: Available from 1 to 37 pairs.
Construction Details

| Item | Code | Material / Description |
|---|---|---|
| Series Code | CH | Marine & Offshore Symmetrical Communication Cable |
| Conductor | / | Tinned / Plain Stranded, Annealed Copper Wire |
| Insulation | J | Mica Glass Tape + XLPE (Cross-linked Polyethylene) Insulation |
| Inner Sheath | PF | Thermoplastic Polyolefin (SHF1) |
| Armor | 9 | Galvanized Steel Wire Braid |
| Outer Sheath | 6 | Thermoplastic Polyolefin (SHF1) |
| Sheath Color | / | Standard Black (Other Colors Available) |
| Flammability | NC | Halogen Free Low Smoke Fire Resistant |
Standards & Compliance
This cable is manufactured in full compliance with the following international standards:
-
General Design: IEC 60092-350, IEC 60092-376
-
Conductor: IEC 60228
-
Insulation & Sheath: IEC 60092-360
-
Fire Resistant: IEC 60331
-
Flame Retardant: IEC 60332-1, IEC 60332-3-22
-
Halogen Free: IEC 60754
-
Low Smoke Emission: IEC 61034
Applications
This cable is engineered for mission-critical systems requiring both fire integrity and mechanical resilience in:
-
Essential telecommunication, data processing, and instrumentation networks on ships, oil & gas platforms, and offshore structures.
-
Critical communication links in heavy industrial and hazardous environments such as power plants, chemical processing facilities, metallurgy, and mining operations, especially for exposed or vulnerable cable runs.