Cable Tray Use (UL) Telephone Central Office Power Cable Specifications

Parameter
Parameter Condition Value Unit
Conductor resistance 2,5 mm² max 8,21 ohm/km
Conductor resistance 6 mm² max 3,39 ohm/km
Conductor resistance 10 mm² max 1,95 ohm/km
Conductor resistance 16 mm² max 1,24 ohm/km
Test voltage f=50Hz, 1 minute 2 kV AC
Operating voltage max 100 V
Operating temperature -20 (-40 when fixed) to +90 ºC
Bending radius 8 x outer diameter mm
Fire resistance IEC60332-3-24

TFL Cable

Product number Cross Section (mm²/AWG) Insulation Color Sheath Color Insulation Thickness (mm) Sheath Diameter (mm) Weight (kg/100m)
TFL492322 2x2.5 (14 AWG) Black, grey Grey 0.60 7.3x7.0 10
TFL492324 2x6 (10 AWG) Black, grey Grey 0.70 9.5x9.5 19
TFL492324/0 2x6 (10 AWG) Black, grey Black (UV-stabilized) 0.70 9.5x9.5 19
TFL492325/0 2x10 (8 AWG) Black, grey Black (UV-stabilized) 0.70 11.5x10.5 29
TFL492326/0 2x16 (6 AWG) Black, grey Black (UV-stabilized) 0.70 13.6x11.8 42

/0 = Black sheath with UV protection (UL 1581).